Network Working Group
Internet Engineering Task Force (IETF)                   J. Quittek, Ed.
Internet-Draft
Request for Comments: 6988                               NEC Europe Ltd.
Category: Informational                                  M. Chandramouli
Intended status: Informational
ISSN: 2070-1721                                      Cisco Systems, Inc.
Expires: November 03, 2013
                                                               R. Winter
                                                         NEC Europe Ltd.
                                                                T. Dietz
                                                         NEC Europe Ltd.
                                                               B. Claise
                                                     Cisco Systems, Inc.
                                                            May 02,
                                                          September 2013

                   Requirements for Energy Management
                    draft-ietf-eman-requirements-14

Abstract

   This document defines requirements for standards specifications for
   energy management.
   Energy Management.  The requirements defined in this document concern are
   concerned with monitoring functions as well as control functions.
   Monitoring functions include identification of identifying energy-managed devices and
   their components, as well as monitoring of their power states, power inlets, power
   outlets, Power States, Power
   Inlets, Power Outlets, actual power (the instantaneous power, as opposed to the
   demand, which is an averaged power), power attributes, Power Attributes, received
   energy, provided energy, and contained batteries.  Control functions
   serve for
   include such functions as controlling power supply and power state Power State of
   energy-managed devices and their components.

   This document does not specify the features that must be implemented
   by compliant implementations but rather lists features that must be
   supported by standards for energy management. Energy Management.

Status of This Memo

   This Internet-Draft document is submitted in full conformance with the
   provisions of BCP 78 and BCP 79.

   Internet-Drafts are working documents not an Internet Standards Track specification; it is
   published for informational purposes.

   This document is a product of the Internet Engineering Task Force
   (IETF).  Note that other groups may also distribute
   working documents as Internet-Drafts.  The list  It represents the consensus of current Internet-
   Drafts is at http://datatracker.ietf.org/drafts/current/.

   Internet-Drafts are draft documents valid the IETF community.  It has
   received public review and has been approved for publication by the
   Internet Engineering Steering Group (IESG).  Not all documents
   approved by the IESG are a maximum candidate for any level of Internet
   Standard; see Section 2 of RFC 5741.

   Information about the current status of six months this document, any errata,
   and how to provide feedback on it may be updated, replaced, or obsoleted by other documents obtained at any
   time.  It is inappropriate to use Internet-Drafts as reference
   material or to cite them other than as "work in progress."

   This Internet-Draft will expire on November 03, 2013.
   http://www.rfc-editor.org/info/rfc6988.

Copyright Notice
   Copyright (c) 2013 IETF Trust and the persons identified as the
   document authors.  All rights reserved.

   This document is subject to BCP 78 and the IETF Trust's Legal
   Provisions Relating to IETF Documents
   (http://trustee.ietf.org/license-info) in effect on the date of
   publication of this document.  Please review these documents
   carefully, as they describe your rights and restrictions with respect
   to this document.  Code Components extracted from this document must
   include Simplified BSD License text as described in Section 4.e of
   the Trust Legal Provisions and are provided without warranty as
   described in the Simplified BSD License.

Table of Contents

   1.  Introduction  . . . . . . . . . . . . . . . . . . . . . . . .   3   2
     1.1.  Conventional Requirements For for Energy Management . . . . .   4   3
     1.2.  Specific Requirements For for Energy Management . . . . . . .   4
   2.  Terminology . . . . . . . . . . . . . . . . . . . . . . . . .   5
   3.  General Considerations Related To to Energy Management . . . . .   6
     3.1.  Power States  . . . . . . . . . . . . . . . . . . . . . .   7   6
     3.2.  Saving Energy Versus versus Maintaining Service Level  . . . . .   7
     3.3.  Local Versus versus Network-Wide Energy Management . . . . . . .   7
     3.4.  Energy Monitoring Versus versus Energy Saving  . . . . . . . . .   8
     3.5.  Overview Of of Energy Management Requirements  . . . . . . .   8
   4.  Identification Of of Entities  . . . . . . . . . . . . . . . . .   9
   5.  Information On on Entities . . . . . . . . . . . . . . . . . . .  10
     5.1.  General Information On on Entities . . . . . . . . . . . . .  10
     5.2.  Power Interfaces  . . . . . . . . . . . . . . . . . . . .  11
     5.3.  Power . . . . . . . . . . . . . . . . . . . . . . . . . .  13
     5.4.  Power State . . . . . . . . . . . . . . . . . . . . . . .  15
     5.5.  Energy  . . . . . . . . . . . . . . . . . . . . . . . . .  17
     5.6.  Battery State . . . . . . . . . . . . . . . . . . . . . .  18  17
     5.7.  Time Series Of of Measured Values  . . . . . . . . . . . . .  19
   6.  Control Of of Entities . . . . . . . . . . . . . . . . . . . . .  21  20
   7.  Reporting On on Other Entities . . . . . . . . . . . . . . . . .  21
   8.  Controlling Other Entities  . . . . . . . . . . . . . . . . .  22
     8.1.  Controlling Power States Of of Other Entities  . . . . . . .  22
     8.2.  Controlling Power Supply  . . . . . . . . . . . . . . . .  23
   9.  Security Considerations . . . . . . . . . . . . . . . . . . .  23
   10. IANA Considerations . . . . . . . . . . . . . . . . . . . . .  24
   11. Acknowledgments . . . . . . . . . . . . . . . . . . . . . . .  25
   12.
   11. References  . . . . . . . . . . . . . . . . . . . . . . . . .  25
     12.1.
     11.1.  Normative References . . . . . . . . . . . . . . . . . .  25
     12.2.
     11.2.  Informative References . . . . . . . . . . . . . . . . .  26
   Authors' Addresses  . . . . . . . . . . . . . . . . . . . . . . .  27

1.  Introduction
   With rising energy cost costs and with an increasing awareness of the
   ecological impact of running information technology equipment, energy
   management Energy
   Management (EMAN) functions and interfaces are becoming an additional
   basic requirement for network management systems and devices
   connected to a network.

   This document defines requirements for standards specifications for
   energy management,
   Energy Management, both monitoring functions and control functions.
   The main subject of energy management are entities in the network,
   i.e.  device or one of a device's components, that receive and
   provide electric energy.  Devices may have an IP address, such as
   hosts, routers, and middleboxes, or they are connected indirectly to
   the Internet via a proxy with an IP address providing a management
   interface for the device.  An example are devices in a building
   infrastructure using non-IP protocols and a gateway to the Internet.

   The main subject of energy management are
   Energy Management functions focus mainly on devices and their
   components that receive and provide electric electrical energy.  Devices may
   have an IP address, such
   as hosts, routers, and middleboxes, middleboxes may have an IP address or they
   might may be
   connected indirectly to the Internet via a proxy with an IP address
   providing a management interface for the device.  An example
   are device, for example, devices
   in a building infrastructure using non-IP protocols and a gateway to
   the Internet.

   These requirements concern are concerned with the standards specification
   process and not the implementation of specified standards.  All
   requirements in this document must be reflected by standards
   specifications to be developed.  However, which of the features
   specified by these standards will be mandatory, recommended, or
   optional for compliant implementations is to be defined by standards track Standards
   Track document(s) and not in this document.

   Section 3 elaborates on a set of general needs for energy management. Energy Management.
   Requirements for an energy management Energy Management standard are specified in
   Sections 4 to through 8.

   Sections 4 to through 6 contain conventional requirements specifying
   information on entities and control functions.

   Sections 7 and 8 contain requirements specific to energy management. Energy Management.
   Due to the nature of power supply, some monitoring and control
   functions are not conducted by interacting with the entity of
   interest,
   interest but rather with other entities, for example, entities
   upstream in a power distribution tree.

1.1.  Conventional Requirements For for Energy Management

   The specification of requirements for an energy management Energy Management standard
   starts with Section 4 addressing 4, which addresses the identification of entities
   and the granularity of reporting of energy-related information.  A
   standard must support the unique identification of entities,
   reporting per entire device, and reporting energy-related information
   on individual components of a device or attached devices.

   Section 5 specifies requirements related to the monitoring of
   entities.  This includes general (type, context) information and
   specific information on Power States, power inlets, power outlets, Power Inlets, Power Outlets,
   power, energy, and batteries.  Control  The control of Power State and power
   supply of by entities is covered by requirements specified in Section 6.

1.2.  Specific Requirements For for Energy Management

   While the conventional requirements summarized above seem to be all
   that would be needed for energy management, Energy Management, there are significant
   differences between energy management Energy Management and most well known well-known network
   management functions.  The most significant difference is the need
   for some devices to report on other entities.  There are three major
   reasons for this.

   o  For monitoring a particular entity entity, it is not always sufficient to
      communicate only with the entity only. that entity.  When the entity has no
      instrumentation for determining power, it might still be possible
      to obtain power values for the entity by via communication with other
      entities in its power distribution tree.  A simple example is retrieving of this
      would be the retrieval of power values from a power meter at the
      power line into the entity.  Common examples are a  A Power Distribution Unit (PDU) and a
      Power over Ethernet (PoE) switch. switch are common examples.  Both supply
      power to other entities at sockets or ports, respectively, and are
      often instrumented to measure power per socket or port.

   o  Similar considerations apply to controlling the power supply of a an
      entity which that often needs direct or indirect communications with
      another entity upstream in the power distribution tree.  Again, a
      PDU and a PoE switch are common examples, if they have the
      capability to switch power on or off power at their sockets or ports,
      respectively.

   o  Energy management Management often extends beyond entities with IP network
      interfaces,
      interfaces to non-IP building systems accessed via a gateway
      (sometimes called an energy management system Energy Management System or controller).
      Requirements in this document do not cover the details of these
      networks and energy devices, devices but specify means for opening IP
      network management towards them.

   These specific issues of energy management and a set of further ones Energy Management, as well as other issues,
   are covered by requirements specified in Sections 7 and 8.

   The requirements in these sections need a new energy management Energy Management
   framework that deals with the specific nature of energy management. Energy Management.
   The actual standards documents, such as MIB module specifications,
   address conformance by specifying which feature features must, should, or may
   be implemented by compliant implementations.

2.  Terminology

   The terms specified in the terminology section are capitalized
   throughout the document; the exceptions are the well-known terms
   "energy" and "power".  These terms are generic and are used in
   generated terms such as "energy-saving", "low-power", etc.

   Energy

      Energy

      That which does work or is capable the capacity of doing a system to do work.  As used by
      electric utilities, it is generally a reference to electrical
      energy and is measured in kilo-watt hours kilowatt-hours (kWh) [IEEE-100].

   Power

      The

      Power is the time rate at which Energy energy is emitted, transferred, or
      received; power is usually expressed in watts (or in joules per
      second) [IEEE-100].  (The term "power" does not refer to the
      concept of demand, which is an averaged power value.)

   Power Attributes

      Power Attributes

      Measurements are measurements of the electrical electric current, voltage, phase
      phase, and frequencies at a given point in an electrical power system.
      Reference: Adapted
      system (adapted from [IEC60050]

      NOTES: 1. [IEC.60050]).

      NOTE: Power Attributes is are not intended to be judgmental "judgmental" with
      respect to a reference or technical value and are independent of
      any usage context.

   Energy Management

      Energy Management is a set of functions for measuring, modeling,
      planning, and optimizing networks to ensure that the network
      elements and attached devices use energy efficiently and in a
      manner appropriate to the nature of the application and the cost
      constraints of the organization [ITU-M.3400].

   Energy Management System

      An Energy Management System is a combination of hardware and
      software used to administer a network with the primary purpose
      being Energy Management [Fed-Std-1037C]. Management.

   Energy Monitoring
      Energy Monitoring is a part of Energy Management that deals with
      collecting or reading information from network elements and
      attached devices and their components to aid in Energy Management.

   Energy Control

      Energy Control is a part of Energy Management that deals with
      controlling energy supply and power state Power State of network elements and elements, as
      well as attached devices and their components.

   Power Interface

      A Power Interface is an interface at which a device is connected
      to a Power power transmission medium medium, at which it can in turn receive Power,
      power, provide Power, power, or both.

   Power Inlet

      A Power Inlet is a Power Interface at which a device can receive
      Power
      power from other devices.

   Power Outlet

      A Power Outlet is a Power Interface at which a device can provide
      Power
      power to other devices.

   Power State

      A Power State is a condition or mode of a device that broadly
      characterizes its capabilities, Power power consumption, and
      responsiveness to input [IEEE-1621].

3.  General Considerations Related To to Energy Management

   The basic objective of Energy Management is operating to operate sets of
   devices
   with using minimal Energy, energy, while maintaining a certain level of
   service.
   [I-D.ietf-eman-applicability-statement]  [EMAN-STATEMENT] presents the applicability of the EMAN
   framework to a variety of scenarios, scenarios and also lists use cases and
   target devices.

3.1.  Power States

   Entities can be set to an operational state that results in the
   lowest power level that still meets the service level service-level performance
   objectives.  In principle, there are three basic types of Power
   States for an entity or for a whole system:

   o  full Power State
   o  sleep state (not functional, functional but immediately available)

   o  off state (may require significant time to become operational)

   In specific devices, the number of Power States and their properties
   varies
   vary considerably.  Simple entities may just have only have the extreme
   states, states:
   full power Power State and off state.  Many devices have three basic Power
   States: on, off, and sleep.  However, more finely grained Power
   States can be implemented.  Examples are various operational low
   power states
   Power States in which a device requires less energy than in the full
   power "on" state, but - -- compared to the sleep state - -- is still
   operational with reduced performance or functionality.

3.2.  Saving Energy Versus versus Maintaining Service Level

   One of the objectives of Energy Management is to reduce the Energy energy
   consumption.  While this objective is clear, the way to attain attaining that goal is
   often difficult.  In many cases cases, there is no way of reducing to reduce power
   without the consequence of a potential service (performance or
   capacity) degradation.  In this case, a trade-off needs to be made
   between service level service-level objectives and energy minimization.  In other
   cases
   cases, a reduction of power can easily be achieved while still
   maintaining sufficient service level service-level performance, for example, by
   switching entities to lower Power States when higher performance is
   not needed.

3.3.  Local Versus versus Network-Wide Energy Management

   Many Energy saving energy-saving functions are executed locally by an entity; it
   monitors its usage and dynamically adapts its Power power according to the
   required performance.  It may, for example, switch to a sleep state
   when it is not in use use, or out outside of scheduled business hours.  An
   Energy Management System may observe an entity's Power State and
   configure its Power saving power-saving policies.

   Energy savings can also be achieved with policies implemented by a
   network management system that controls Power States of managed
   entities.  Information about the Power power received and provided by
   entities in different Power States may be required in order to set
   such policies.
   Often  Often, this information is acquired best acquired through
   monitoring.

   Both methods, network-wide

   Network-wide and local Energy Management, Management methods both have advantages
   and disadvantages disadvantages, and often it is often desirable to combine them.
   Central management is often favorable for setting Power States of a
   large number of entities at the same time, for example, at the
   beginning and end of business hours in a building.  Local management
   is often preferable for Power saving power-saving measures based on local
   observations, such as the high or low functional load of an entity.

3.4.  Energy Monitoring Versus versus Energy Saving

   Monitoring Energy, Power, energy, power, and Power States alone does not reduce the
   Energy
   energy needed to run an entity.  In fact, it may even increase it
   slightly due to monitoring instrumentation that needs Energy. energy.
   Reporting measured quantities over the network may also increase
   Energy
   energy use, though the acquired information may be an essential input
   to control loops that save Energy. energy.

   Monitoring Energy energy and Power States can also be required for other
   purposes
   purposes, including:

   o  investigating Energy saving energy-saving potential

   o  evaluating the effectiveness of Energy saving energy-saving policies and
      measures

   o  deriving, implementing, and testing Power power management strategies

   o  accounting for the total Power power received and provided by an entity,
      a network, or a service

   o  predicting an entity's reliability based on Power power usage

   o  choosing the time of the next maintenance cycle for an entity

3.5.  Overview Of of Energy Management Requirements

   The following basic management functions are required:

   o  monitoring Power States

   o  monitoring Power (Energy power (energy conversion rate)

   o  monitoring (accumulated) received and provided Energy energy

   o  monitoring Power attributes Attributes

   o  setting Power States
   Power control is complementary to other Energy savings measures energy-saving measures, such
   as low-power electronics, Energy saving energy-saving protocols, energy-efficient
   device design (for example, low-power modes for components), and
   energy-efficient network architectures.  Measurement of received and
   provided Energy energy can provide useful data for developing these
   technologies.

4.  Identification Of of Entities

   Entities must be capable of being uniquely identified with within the
   context of the management system.  This includes entities that are
   components of managed devices as well as entire devices.

   Entities that report on or control other entities must identify the
   entities they report on or control: see Section 7 or Section 8,
   respectively, for the detailed requirements.

   An entity may be an entire device or a component of it.  Examples of
   components of interest are a hard drive, a battery, or a line card.
   It may be required to be able
   The ability to control individual components to save Energy. energy may be
   required.  For example, server blades can be switched off when the
   overall load is low low, or line cards at switches may be powered down at
   night.

   Identifiers for devices and components are already defined in
   standard MIB modules, such as the LLDP Link Layer Discovery Protocol
   (LLDP) MIB module [IEEE-802.1AB] and the LLDP-MED Link Layer Discovery
   Protocol -- Media Endpoint Discovery (LLDP-MED) MIB module
   [ANSI-TIA-1057] for devices devices, and the Entity MIB module [RFC4133] [RFC6933] and
   the Power power Ethernet MIB [RFC3621] for components of devices.  Energy
   Management needs a means to link Energy-
   related energy-related information to such
   identifiers.

   Instrumentation for measuring the received and provided Energy energy of a
   device is typically more expensive than instrumentation for
   retrieving its Power State.  Many devices may provide Power State
   information for all individual components separately, while reporting
   the received and provided Energy energy only for the entire device.

4.1.  Identifying Entities

   The standard must provide means for uniquely identifying entities.
   Uniqueness must be preserved such that collisions of identities are
   avoided at potential receivers of monitored information.

4.2.  Persistence Of of Identifiers
   The standard must provide means for indicating whether identifiers of
   entities are persistent across a re-start restart of the entity.

4.3.  Change Of of Identifiers

   The standard must provide means to indicate any change of entity
   identifiers.

4.4.  Using Entity Identifiers Of of Existing MIB Modules

   The standard must provide means for re-using reusing entity identifiers from
   existing standards standards, including at least the following:

   o  the entPhysicalIndex in the Entity MIB module [RFC4133] [RFC6933]

   o  the LldpPortNumber in the LLDP MIB module [IEEE-802.1AB] and in
      the LLDP-MED MIB module [ANSI-TIA-1057]

   o  the pethPsePortIndex and the pethPsePortGroupIndex in the Power
      Ethernet MIB [RFC3621]

   Generic means for re-using reusing other entity identifiers must be provided.

5.  Information On on Entities

   This section describes information on entities for which the standard
   must provide means for retrieving and reporting.

   Required information can be structured into seven groups.
   Section 5.1 specifies requirements for general information on
   entities, such as type of entity or context information.
   Requirements for information on Power Inlets and Power Outlets of
   entities are specified in Section 5.2.  Monitoring  The monitoring of Power power and
   Energy
   energy is covered by Sections 5.3 and 5.5, respectively.  Section 5.4
   covers requirements related to entities' Power States.  Section 5.6
   specifies requirements for monitoring batteries.  Finally, the
   reporting of time series of values is covered by Section 5.7.

5.1.  General Information On on Entities

   For Energy Management it may be required to understand Management, understanding the role and context of an entity.
   entity may be required.  An Energy Management System may aggregate
   values of received and provided Energy energy according to a defined
   grouping of entities.  When controlling and setting Power States States, it
   may be helpful to understand the grouping of the entity and role of
   an entity in a network, for network.  For example, it may be important to exclude
   some mission critical mission-critical network devices from being switched to lower
   Power
   power or even from being switched off.

5.1.1.  Type Of of Entity

   The standard must provide means to configure, retrieve retrieve, and report a
   textual name or a description of an entity.

5.1.2.  Context Of An of an Entity

   The standard must provide means for retrieving and reporting context
   information on entities, for example, tags associated with an entity
   that indicate the entity's role.

5.1.3.  Significance Of of Entities

   The standard must provide means for retrieving and reporting the
   significance of entities within its context, for example, how
   important the entity is.

5.1.4.  Power Priority

   The standard must provide means for retrieving and reporting Power power
   priorities of entities.  Power priorities indicate an order in which
   Power States of entities are changed, for example, to lower Power
   States for saving Power. power.

5.1.5.  Grouping Of of Entities

   The standard must provide means for grouping entities.  This can be
   achieved in multiple ways, for example, by providing means to tag
   entities, to assign them to domains, or to assign device types to them.

5.2.  Power Interfaces

   A Power Interface is an interface at which a device is connected to a
   Power
   power transmission medium medium, at which it can in turn receive Power, power,
   provide
   Power, power, or both.

   A Power Interface is either an inlet or an outlet.  Some Power
   Interfaces change over time from being an inlet to being an outlet
   and vice versa.  However  However, most Power Interfaces never change.

   Devices have Power Inlets at which they are supplied with electric
   Power.
   power.  Most devices have a single Power Inlet, while some have
   multiple inlets.  Different Power Inlets on a device are often
   connected to separate Power power distribution trees.  For Energy
   Monitoring, it is useful to retrieve information on the number of
   inlets of a device, the availability of Power power at inlets inlets, and which of
   them
   inlets are actually in use.

   Devices can have one or more Power Outlets for supplying other
   devices with electric Power. power.

   For identifying and potentially controlling the source of Power power
   received at an inlet, it may be required to identify identifying the Power Outlet of another device
   at which the received Power power is provided. provided may be required.
   Analogously, for each outlet outlet, it is of interest to identify the Power
   Inlets that receive the Power power provided at a certain outlet.  Such
   information is also required for constructing the wiring topology of
   electrical Power power distribution to devices.

   Static properties of each Power Interface are required information
   for Energy Management.  Static properties include the kind of
   electric current (AC or DC), the nominal voltage, the nominal AC
   frequency, and the number of AC phases.  Note that often the nominal
   voltage is often not a single value but a voltage range, such as, for
   example, (100V-120V), (100V-240V), (100V-120V,220V-240V).

5.2.1.  Lists Of  List of Power Interfaces

   The standard must provide means for monitoring the list of Power
   Interfaces of a device.

5.2.2.  Operational Mode Of of Power Interfaces

   The standard must provide means for monitoring the operational mode
   of a Power Interface Interface, which is either "Power Inlet" or "Power
   Outlet".

5.2.3.  Corresponding Power Outlet

   The standard must provide means for identifying the Power Outlet that
   provides the Power power received at a Power Inlet.

5.2.4.  Corresponding Power Inlets

   The standard must provide means for identifying the list of Power
   Inlets that receive the Power power provided at a Power Outlet.

5.2.5.  Availability Of of Power

   If the Power States allow it, the standard must provide means for
   monitoring the availability of Power power at each Power Interface.  This
   indicates
   includes indicating whether a power supply at a Power Interfaces Power supply Interface is
   switched on or off.

5.2.6.  Use Of of Power
   The standard must provide means for monitoring for each Power Interface
   if it is actually in actual use.  For inlets inlets, this means that the device
   actually receives Power power at the inlet.  For outlets outlets, this means that Power
   power is actually provided from it the outlet to one or more devices.

5.2.7.  Type Of current of Current

   The standard must provide means for reporting the type of current (AC
   or DC) for each Power Interface as well as for a device.

5.2.8.  Nominal Voltage Range

   The standard must provide means for reporting the nominal voltage
   range for each Power Interface.

5.2.9.  Nominal AC Frequency

   The standard must provide means for reporting the nominal AC
   frequency for each Power Interface.

5.2.10.  Number Of of AC Phases

   The standard must provide means for reporting the number of AC phases
   for each Power Interface.

5.3.  Power

   Power is measured as an instantaneous value or as the average over a
   time interval.

   Obtaining highly accurate values for Power power and Energy energy may be costly
   if it requires dedicated metering hardware. hardware is required.  Entities without the
   ability to measure with high accuracy their Power and power, received energy,
   and provided Energy with
   high accuracy energy may just report estimated values, for example example,
   based on load monitoring, Power State, or even just the entity type.

   Depending on how Power power and Energy energy values are obtained, the confidence
   in the a reported value and its accuracy will vary.  Entities reporting
   such values should qualify the confidence in the reported values and
   quantify the accuracy of measurements.  For reporting accuracy, the
   accuracy classes specified in IEC 62053-21 [IEC.62053-21] and IEC
   62053-22 [IEC.62053-22] should be considered.

   Further properties of the Power power supplied to a device are also of
   interest.  Particularly for  For AC Power supply, power supply in particular, several Power attributes
   Attributes beyond the real Power power are of potential interest to Energy
   Management Systems.  The set of these properties include the includes the complex
   Power
   attributes Attributes (apparent power, reactive power, and phase angle of
   the current or power factor) as well as the actual voltage, the
   actual AC frequency, the Total Harmonic Distortion (THD) of voltage
   and current, and the impedance of an AC phase or of the DC supply.  A
   new standard for monitoring these Power attributes Attributes should be in line
   with
   already existing already-existing standards, such as [IEC.61850-7-4].

   For some network management tasks tasks, it is desirable to receive
   notifications from entities when their Power power value exceeds or falls
   below given thresholds.

5.3.1.  Real Power / Power Factor

   The standard must provide means for reporting the real power for each
   Power Interface as well as for an entity.  Reporting Power power includes
   reporting the direction of Power power flow.

5.3.2.  Power Measurement Interval

   The standard must provide means for reporting the corresponding time
   or time interval for which a Power power value is reported.  The Power power
   value can be measured at the corresponding time or averaged over the
   corresponding time interval.

5.3.3.  Power Measurement Method

   The standard must provide means to indicate the method how used to obtain
   these
   values have been obtained. values.  Based on how the measurement was conducted, it is
   possible to associate a certain degree of confidence with the
   reported Power power value.  For example, there are methods of measurement
   such as direct Power power measurement, or by estimation based on performance
   values, or hard coding hard-coding average Power power values for an entity.

5.3.4.  Accuracy Of of Power And and Energy Values

   The standard must provide means for reporting the accuracy of
   reported Power power and Energy energy values.

5.3.5.  Actual Voltage And and Current

   The standard must provide means for reporting the actual voltage and
   actual current for each Power Interface as well as for a device.  In
   case of  For
   AC Power power supply, means must be provided for reporting the actual
   voltage and actual current per phase.

5.3.6.  High/low Power  High-Power/Low-Power Notifications

   The standard must provide means for creating notifications if Power power
   values of an entity rise above or fall below given thresholds.

5.3.7.  Complex Power / Power Factor

   The standard must provide means for reporting the complex power for
   each Power Interface and for each phase at a Power Interface.
   Besides  In
   addition to the real power, at least two out of the following three
   quantities need to be reported: apparent power, reactive power, and
   phase angle.  The phase angle can be substituted by the power factor.

5.3.8.  Actual AC Frequency

   The standard must provide means for reporting the actual AC frequency
   for each Power Interface.

5.3.9.  Total Harmonic Distortion

   The standard must provide means for reporting the Total Harmonic
   Distortion (THD) of voltage and current for each Power Interface.  In
   case of
   For AC Power power supply, means must be provided for reporting the THD per
   phase.

5.3.10.  Power Supply Impedance

   The standard must provide means for reporting the impedance of Power a
   power supply for each Power Interface.  In case of  For AC Power power supply, means
   must be provided for reporting the impedance per phase.

5.4.  Power State

   Many entities have a limited number of discrete Power States.

   There is a need to report the actual Power State of an entity, entity and to
   provide the means for retrieving the list of all supported Power
   States.

   Different standards bodies have already defined sets of Power States
   for some entities, and others are creating new Power State sets.  In
   this context, it is desirable that the standard support many of these
   Power State standards.  In order to support multiple management
   systems that possibly using use different Power State sets, sets while
   simultaneously interfacing with a particular entity, the Energy
   Management standard System must provide means for supporting multiple Power
   State sets used simultaneously at an entity.

   Power States have parameters that describe its their properties.  It is
   required to have a standardized means for reporting some key
   properties, such as the typical Power power of an entity in a certain
   state.

   There also is also a need to report statistics on Power States States, including
   the time spent and as well as the received and provided Energy energy in a Power
   State.

5.4.1.  Actual Power State

   The standard must provide means for reporting the actual Power State
   of an entity.

5.4.2.  List Of of Supported Power States

   The standard must provide means for retrieving the list of all
   potential Power States of an entity.

5.4.3.  Multiple Power State Sets

   The standard must provide means for supporting multiple Power State
   sets simultaneously at an entity.

5.4.4.  List Of of Supported Power State Sets

   The standard must provide means for retrieving the list of all Power
   State sets supported by an entity.

5.4.5.  List Of of Supported Power States Within A within a Set

   The standard must provide means for retrieving the list of all
   potential Power States of an entity for each supported Power State
   set.

5.4.6.  Typical Power Per Power State

   The standard must provide means for retrieving the typical Power power for
   each supported Power State.

5.4.7.  Power State Statistics

   The standard must provide means for monitoring statistics per Power
   State
   State, including the total time spent in a Power State, the number of
   times each state was entered entered, and the last time each state was
   entered.  More Power State statistics are addressed by requirement the
   requirements in Section 5.5.3.

5.4.8.  Power State Changes

   The standard must provide means for generating a notification when
   the actual Power State of an entity changes.

5.5.  Energy

   Monitoring

   The monitoring of electrical Energy energy received or provided by an entity
   is a core function of Energy Management.  Since Energy energy is an
   accumulated quantity, it is always reported for a certain interval of
   time.  This can be, for example, the time from the last restart of
   the entity to the reporting time, the time from another past event to
   the reporting time, the last given amount of time before the
   reporting time, or a certain interval specified by two time stamps timestamps in
   the past.

   It is useful for entities to record their received and provided
   Energy
   energy per Power State and report these quantities.

5.5.1.  Energy Measurement

   The standard must provide means for reporting measured values of
   Energy
   energy and the direction of the Energy energy flow received or provided by
   an entity.  The standard must also provide the means to report the
   Energy
   energy passing through each Power Interface.

5.5.2.  Time Intervals

   The standard must provide means for reporting the time interval for
   which an Energy energy value is reported.

5.5.3.  Energy Per Power State

   The standard must provide means for reporting the received and
   provided Energy energy for each individual Power State.  This extends the
   requirement 5.4.7
   requirements on Power State statistics. statistics described in Section 5.4.7.

5.6.  Battery State

   Batteries are special entities that supply Power. power.  The status of
   these batteries is typically controlled by automatic functions that
   act locally on the entity entity, and manually by users of the entity.
   There is a need to monitor the battery status of these entities by
   network management systems.

   Devices containing batteries can be modeled in two ways.  The entire
   device can be modeled as a single entity on which Energy-related energy-related
   information is reported reported, or the battery can be modeled as an
   individual entity for which Energy-related energy-related information is monitored
   individually according to requirements in Sections 5.1 to through 5.5.

   Further information on batteries is of interest for Energy
   Management, such as the current charge of the battery, the number of
   completed charging cycles, the charging state of the battery, its
   temperature, and further additional static and dynamic battery properties.
   It is desirable to receive notifications if the charge of a battery
   becomes very low or if a battery needs to be replaced.

5.6.1.  Battery Charge

   The standard must provide means for reporting the current charge of a
   battery, in units of milliampere hours milliampere-hours (mAh).

5.6.2.  Battery Charging State

   The standard must provide means for reporting the charging state
   (charging, discharging, etc.) of a battery.

5.6.3.  Battery Charging Cycles

   The standard must provide means for reporting the number of completed
   charging cycles of a battery.

5.6.4.  Actual Battery Capacity

   The standard must provide means for reporting the actual capacity of
   a battery.

5.6.5.  Actual Battery Capacity Temperature

   The standard must provide means for reporting the actual temperature
   of a battery.

5.6.6.  Static Battery Properties

   The standard must provide means for reporting static properties of a
   battery, including the nominal capacity, the number of cells, the
   nominal voltage, and the battery technology.

5.6.7.  Low battery Battery Charge Notification

   The standard must provide means for generating a notification when
   the charge of a battery decreases below a given threshold.  Note that
   the threshold may depend on the battery technology.

5.6.8.  Battery Replacement Notification

   The standard must provide means for generating a notification when
   the number of charging cycles of a battery exceeds a given threshold.

5.6.9.  Multiple Batteries

   If the battery technology allows, the standard must provide means for
   meeting requirements in Sections 5.6.1 to through 5.6.8 for each
   individual battery contained in a single entity.

5.7.  Time Series Of of Measured Values

   For some network management tasks, it is required to obtain obtaining time series of measured
   values from entities, such as Power, Energy, power, energy, battery charge, etc. etc., is
   required.

   In general general, time series measurements could be obtained in many
   different ways.  Means should be provided to either push such values
   from the location where they are available to the management system
   or to have them stored locally for a sufficiently long period of time
   such that a management system can retrieve the full time series.

   The following issues are to be considered when designing time series
   measurement and reporting functions:

   1.  Which quantities should be reported?

   2.  Which time interval type should be used (total, delta, sliding
       window)?

   3.  Which measurement method should be used (sampled, continuous)?

   4.  Which reporting model should be used (push or pull)?

   The most discussed and probably most needed quantity is Energy. energy.  But
   a need for others, such as Power power and battery charge charge, can be
   identified as well.

   There are three time interval types under discussion for accumulated
   quantities such as Energy. energy.  They can be reported as total values,
   accumulated between the last restart of the measurement and a certain
   timestamp.  Alternatively, Energy energy can be reported as delta values
   between two consecutive timestamps.  Another alternative is reporting
   values for sliding windows as specified in [IEC.61850-7-4].

   For non-accumulative quantities, such as Power, power, different measurement
   methods are considered.  Such quantities can be reported using values
   sampled at certain time stamps or alternatively timestamps or, alternatively, by mean values for
   these quantities averaged between two (consecutive) time stamps timestamps or
   over a sliding window.

   Finally, time series can be reported using different reporting
   models, particularly push-based or pull-based.  Push-based reporting
   can, for example, be realized by reporting Power power or Energy energy values
   using the IPFIX IP Flow Information Export (IPFIX) protocol [RFC5101],[RFC5102].  SNMP [RFC5101]
   [RFC5102].  The Simple Network Management Protocol (SNMP) [RFC3411]
   is an example for of a protocol that can be used for realizing pull-based
   reporting of time series.

   For reporting time series of measured values values, the following
   requirements have been identified.  Further decisions concerning
   issues discussed above need to be made when developing concrete
   Energy Management standards.

5.7.1.  Time Series Of of Energy Values

   The standard must provide means for reporting time series of Energy energy
   values.  If the comparison of time series between multiple entities
   is required, then time synchronization between those entities must be
   provided (for example, with the Network Time Protocol [RFC5905]).

5.7.2.  Time Series Interval Types

   The standard must provide means for supporting alternative interval
   types.  Requirement  The requirement in Section 5.5.2 applies to every reported
   time value.

5.7.3.  Time Series Storage Capacity

   The standard should provide means for reporting the number of values
   of a time series that can be stored for later reporting.

6.  Control Of of Entities

   Many entities control their Power State locally.  Other entities need
   interfaces for an Energy Management System to control their Power
   State.

   Power

   A power supply is typically not self-managed by devices.  And
   controlling Power devices, and control
   of a power supply is typically not conducted as an interaction
   between an Energy Management System and the device itself.  It is
   rather an interaction between the management system and a device
   providing
   Power power at its Power Outlets.  Similar to Power State
   control, Power power supply control may be policy driven.  Note that
   shutting down the
   Power power supply abruptly may have severe consequences
   for the device.

6.1.  Controlling Power States

   The standard must provide means for setting Power States of entities.

6.2.  Controlling Power Supply

   The standard must provide means for switching Power a power supply off or
   turning Power a power supply on at Power Interfaces providing Power power to one
   or more device. devices.

7.  Reporting On on Other Entities

   As discussed in Section 5, not all Energy-related energy-related information may be
   available at the concerned entity. entity in question.  Such information may be
   provided by other entities.  This section covers only the reporting
   of information
   only. information.  See Section 8 for requirements on controlling other
   entities.

   There are cases where a Power power supply unit switches Power power for several
   entities by turning Power power on or off at a single Power Outlet or where
   a Power power meter measures the accumulated Power power of several entities at a
   single power line.  Consequently, it should be possible to report
   that a monitored value does not relate to just a single entity, entity but is
   an accumulated value for a set of entities.  All of these the entities
   belonging to that set need to be identified.

7.1.  Reports On on Other Entities

   The standard must provide means for an entity to report information
   on another entity.

7.2.  Identity Of of Other Entities On on Which Information Is Reported

   For entities that report on one or more other entities, the standard
   must provide means for reporting the identity of other entities on
   which information is reported.  Note that, in some situations, a
   manual configuration might be required to populate this information.

7.3.  Reporting Quantities Accumulated Over over Multiple Entities

   The standard must provide means for reporting the list of all
   entities from which contributions are included in an accumulated
   value.

7.4.  List Of of All Entities On on Which Information Is Reported

   For entities that report on one or more other entities, the standard
   must provide means for reporting the complete list of all those
   entities on which Energy-related energy-related information can be reported.

7.5.  Content Of of Reports On on Other Entities

   For entities that report on one or more other entities, the standard
   must provide means for indicating which Energy-related what type or types of energy-
   related information can be reported reported, and for which of those entities.

8.  Controlling Other Entities

   This section specifies requirements for controlling Power States and
   power supply of entities by communicating with other entities that
   have the means for doing that control.

8.1.  Controlling Power States Of of Other Entities

   Some entities have control over Power States of other entities.  For
   example
   example, a gateway to a building system may have the means to control
   the Power State of entities in the building that do not have an IP
   interface.  For this scenario and other similar cases means are
   needed cases, a way to make
   this control accessible to the Energy Management
   System. System is needed.

   In addition to this, addition, it is required that an entity that has its state
   controlled by other entities has the means to report the list of
   these other entities.

8.1.1.  Control Of of Power States Of of Other Entities

   The standard must provide means for an Energy Management System to
   send Power State control commands to an entity that concern controls the
   Power States of entities other than the one entity to which the command
   was sent to. sent.

8.1.2.  Identity Of of Other Power State Controlled Entities

   The standard must provide means for reporting the identities of the
   entities for which the reporting entity has the means to control
   their Power States.  Note that, in some situations, a manual
   configuration might be required to populate this information.

8.1.3.  List Of of All Power State Controlled Entities

   The standard must provide means for an entity to report the list of
   all entities for which it can control the Power State.

8.1.4.  List Of of All Power State Controllers

   The standard must provide means for an entity that receives commands
   controlling its Power State from other entities to report the list of
   all those entities.

8.2.  Controlling Power Supply

   Some entities may have control of the Power power supply of other entities,
   for example, because the other entity is supplied via a Power Outlet
   of the entity.  For this and similar cases cases, means are needed to make
   this control accessible to the Energy Management System.  This need
   is already addressed by the requirement in Section 6.2.

   In addition, it is required that an entity that has its supply
   controlled by other entities has the means to report the list of
   these other entities.  This need is already addressed by requirements
   in Sections 5.2.3 and 5.2.4.

9.  Security Considerations

   Controlling Power State and Power power supply of entities are considered
   highly sensitive actions actions, since they can significantly affect the
   operation of directly and indirectly affected connected devices.  Therefore  Therefore,
   all control actions addressed in sections Sections 6 and 8 must be
   sufficiently protected through authentication, authorization, and
   integrity protection mechanisms.

   Entities that are not sufficiently secure to operate directly on the
   public Internet do exist and can be a significant cause of risk, for
   example, if the remote control functions described in sections Sections 6 and
   8 can be exercised on those devices from anywhere on the Internet.
   The standard needs to provide means for dealing with such cases.  One
   solution is providing means that allow for the isolation of such devices,
   e.g.
   e.g., behind a sufficiently secured gateway.  Another solution is
   allowing to
   allow compliant implementations that have disabled to disable sensitive functions, or to
   not
   implemented sensitive functions.

   Monitoring Energy-related implement such functions at all.

   The monitoring of energy-related quantities of an entity as addressed
   in Sections 5 - through 8 can be used to derive more information than
   just the received and provided Energy, so energy; therefore, monitored data
   requires protection.  This protection includes authentication and
   authorization of entities requesting access to monitored data as well
   as confidentiality protection during transmission of monitored data.
   Privacy of stored data in an entity must be taken into account.
   Monitored data may be used as input to control, accounting, and other
   actions, so integrity of transmitted information and authentication
   of the origin may be needed.

9.1.  Secure Energy Management

   The standard must provide privacy, integrity, and authentication
   mechanisms for all actions addressed in Sections 5 - through 8.  The
   security mechanisms must meet the security requirements elaborated detailed in
   Section 1.4 of [RFC3411].

9.2.  Isolation Of of Insufficiently Secure Entities

   The standard must provide means to allow for the isolation of entities
   that that are not sufficiently secure to operate on the public Internet,
   e.g., behind a gateway that does implement implements sufficient security so that the
   vulnerable entities are not directly exposed to the Internet.

9.3.  Optional Restriction Of of Functions

   The standard must allow for compliant implementations that do to disable
   sensitive functions, or to not implement sensitive such functions or disable them at all, when
   operating in environments that are not sufficiently secured environments. secured.  This
   applies particularly to the control functions described in sections Sections 6
   and 8.

10.  IANA Considerations

   This document has no actions for IANA.

11.  Acknowledgments

   The authors would like to thank Ralf Wolter for his first essay on
   this draft. document.  Many thanks to William Mielke, John Parello,
   JinHyeock Choi, Georgios Karagiannis, and Michael Suchoff for their
   helpful comments on the draft. document.  Many thanks for their IESG reviews to Stephen Farrell,
   Robert Sparks, Adrian Farrel, Barry Leiba, Brian Haberman, Peter
   Resnick, Sean Turner, Stewart Bryant, and Ralph Droms. Droms for their IESG
   reviews.  Finally, special thanks to the document shepherd shepherd, Nevil
   Brownlee, and to the EMAN working group chairs: Nevil Brownlee and
   Bruce Nordman.

12.

11.  References

12.1.

11.1.  Normative References

   [RFC3411]  Harrington, D., Presuhn, R., and B. Wijnen, "An
              Architecture for Describing Simple Network Management
              Protocol (SNMP) Management Frameworks", STD 62, RFC 3411,
              December 2002.

   [RFC3621]  Berger, A. and D. Romascanu, "Power Ethernet MIB", RFC
              3621, December 2003.

   [RFC4133]  Bierman, A. and K. McCloghrie, "Entity MIB (Version 3)",
              RFC 4133, August 2005.

   [ANSI-TIA-1057]
              Telecommunications Industry Association, , "ANSI-
              TIA-1057-2006 - TIA ANSI-
              TIA-1057-2006, "TIA Standard - -- Telecommunications - -- IP
              Telephony Infrastructure - -- Link Layer Discovery Protocol
              for Media Endpoint Devices ", Devices", April 2006.

   [IEEE-100]
              IEEE, , "Authoritative Dictionary of IEEE Standards Terms,
              IEEE 100, Seventh Edition ", December 2000.

   [IEC.61850-7-4]
              International Electrotechnical Commission, "Communication
              networks and systems for power utility automation -- Part
              7-4: Basic communication structure -- Compatible logical
              node classes and data object classes", March 2010.

   [IEC.62053-21]
              International Electrotechnical Commission, , "Electricity
              metering equipment (a.c.) - -- Particular requirements - --
              Part
              22: 21: Static meters for active energy (classes 1 and 2) ",
              2)", January 2003.

   [IEC.62053-22]
              International Electrotechnical Commission, , "Electricity
              metering equipment (a.c.) - -- Particular requirements - --
              Part 22: Static meters for active energy (classes 0,2 S
              and 0,5
              S) ", S)", January 2003.

   [IEC.61850-7-4]
              International Electrotechnical Commission, ,
              "Communication networks and systems for power utility
              automation - Part 7-4: Basic communication structure -
              Compatible logical node classes and data object classes ",
              2010.

   [IEEE-100]
              IEEE, "The Authoritative Dictionary of IEEE Standards
              Terms, IEEE 100, Seventh Edition", December 2000.

   [IEEE-1621]
              Institute of Electrical and Electronics Engineers, , "IEEE
              P1621-2004 -Draft
              1621-2004 - IEEE Standard for User Interface Elements in
              Power Control of Electronic Devices Employed in Office Office/
              Consumer Environments ", June 2005. Environments", 2004.

   [IEEE-802.1AB]
              IEEE Computer Society, , "IEEE Std 802.1AB-2009 - -- IEEE
              Standard for Local and metropolitan area networks - Metropolitan Area Networks --
              Station and Media Access Control Discovery ", Discovery", September
              2009.

12.2.

   [RFC3411]  Harrington, D., Presuhn, R., and B. Wijnen, "An
              Architecture for Describing Simple Network Management
              Protocol (SNMP) Management Frameworks", STD 62, RFC 3411,
              December 2002.

   [RFC3621]  Berger, A. and D. Romascanu, "Power Ethernet MIB", RFC
              3621, December 2003.

   [RFC6933]  Bierman, A., Romascanu, D., Quittek, J., and M.
              Chandramouli, "Entity MIB (Version 4)", RFC 6933, May
              2013.

11.2.  Informative References

   [EMAN-STATEMENT]
              Schoening, B., Chandramouli, M., and B. Nordman, "Energy
              Management (EMAN) Applicability Statement", Work in
              Progress, April 2013.

   [IEC.60050]
              International Electrotechnical Commission, "Electropedia:
              The World's Online Electrotechnical Vocabulary", 2013,
              <http://www.electropedia.org/iev/iev.nsf/
              welcome?openform>.

   [ITU-M.3400]
              International Telecommunication Union, "ITU-T
              Recommendation M.3400 -- Series M: TMN and Network
              Maintenance: International Transmission Systems, Telephone
              Circuits, Telegraphy, Facsimile and Leased Circuits --
              Telecommunications Management Network - TMN management
              functions", February 2000.

   [RFC5101]  Claise, B., "Specification of the IP Flow Information
              Export (IPFIX) Protocol for the Exchange of IP Traffic
              Flow Information", RFC 5101, January 2008.

   [RFC5102]  Quittek, J., Bryant, S., Claise, B., Aitken, P., and J.
              Meyer, "Information Model for IP Flow Information Export",
              RFC 5102, January 2008.

   [RFC5905]  Mills, D., Martin, J., Burbank, J., and W. Kasch, "Network
              Time Protocol Version 4: Protocol and Algorithms
              Specification", RFC 5905, June 2010.

   [I-D.ietf-eman-applicability-statement]
              Schoening, B., Chandramouli, M., and B. Nordman, "Energy
              Management (EMAN) Applicability Statement", draft-ietf-
              eman-applicability-statement-03 (work in progress), April
              2013.

   [Fed-Std-1037C]
              United States National Communications System Technology
              and Standards Division, , "Federal Standard 1037C -
              Telecommunications: Glossary of Telecommunication Terms ",
              August 1996.

   [IEC60050]
              , "International Electrotechnical Vocabulary.
              http://www.electropedia.org/iev/iev.nsf/welcome?openform
              ", .

   [ITU-M.3400]
              International Telecommunication Union, , "ITU-T
              Recommendation M.3400 - Series M: TMN and Network
              Maintenance: International Transmission Systems, Telephone
              Circuits, Telegraphy, Facsimile and Leased Circuits -
              Telecommunications Management Network - TMN management
              functions ", February 2000.

Authors' Addresses

   Juergen Quittek (editor)
   NEC Europe Ltd.
   NEC Laboratories Europe
   Network Research Division
   Kurfuersten-Anlage 36
   Heidelberg  69115
   Germany

   Phone: +49 6221 4342-115
   Email:
   EMail: quittek@neclab.eu

   Mouli Chandramouli
   Cisco Systems, Inc.
   Sarjapur Outer Ring Road
   Bangalore
   India

   Phone: +91 80 4426 3947
   Email:
   EMail: moulchan@cisco.com

   Rolf Winter
   NEC Europe Ltd.
   NEC Laboratories Europe
   Network Research Division
   Kurfuersten-Anlage 36
   Heidelberg  69115
   Germany

   Phone: +49 6221 4342-121
   Email:
   EMail: Rolf.Winter@neclab.eu
   Thomas Dietz
   NEC Europe Ltd.
   NEC Laboratories Europe
   Network Research Division
   Kurfuersten-Anlage 36
   Heidelberg  69115
   Germany

   Phone: +49 6221 4342-128
   Email:
   EMail: Thomas.Dietz@neclab.eu

   Benoit Claise
   Cisco Systems, Inc.
   De Kleetlaan 6a b1
   Diegem  1831
   Belgium

   Phone: +32 2 704 5622
   Email:
   EMail: bclaise@cisco.com